From A-Z how to measure ground resistance with HIOKI FT6041

12/05/2024 14:41:10

Hioki earth resistance measuring equipment is increasingly popular in testing grounding systems in construction sites and factories. But which is the quality product that is most trusted by engineers today? Let's take a look at the Hioki FT604 line of earth resistance measuring equipment for electrical engineers and the most accurate measurement method from the company in this article!

Definition of earth resistance:

Earth resistance is a concept used to refer to the ability of soil to resist electric current, measured by the resistivity of a cube of soil measuring 1m³, with current flowing from one side to the opposite side.

Soil is a porous material with a complex structure consisting of three main components: solid, liquid and gas.  

- Solid: Consists of tiny mineral particles, sizes from 0.1mm to 3mm, and organic compounds from microorganisms and plants.  

- Liquid (soil solution):** This is water containing minerals and dissolved substances from solid and gas particles.  

- Gaseous form: Mainly oxygen, nitrogen and carbon dioxide, filling the pores in the soil.

In soil, the main conductive part is the soil solution. Hard particles such as minerals only conduct electricity very weakly, but when there is a solution containing ions, electric current will be conducted through the movement of ions in an electric field. The higher the ionic concentration of soil, the better its ability to conduct electricity.

Currently, grounding resistance standards have been clearly specified in Vietnamese Standard TCVN 4756:1989. These regulations help construction workers measure and install electrical systems in the most effective and safe way.

Hioki FT6041 earth resistance measuring device can meet most of the criteria:

About measuring function:

Below are the common measurement functions of the Hioki FT6041

- 4-pole measurement method

When conducting a construction design survey, measuring ground resistance is an important step.  

Soil resistance varies depending on the geology of each area. In this process, earth resistance assessment helps determine the optimal location, shape, size and characteristics of ground electrodes before building construction.

- 3-pole measurement method  

This is a method of accurately measuring earth resistance using auxiliary electrodes.  

This method is often applied during post-construction completion inspection or periodic maintenance, ensuring highly reliable measurement values. 

- MEC function 

Earth resistance measurement technology does not require disconnecting the grounding system.  

Incorporating a clamp sensor to measure the current into the electrode under test, MEC helps eliminate influences from surrounding areas. Significantly shortens measurement time.  

- 3-pole measurement method with 4 measuring points  

When the ground resistance value is very small (several ohms or less), the test lead resistance can distort the results.  

The 4-point measurement method overcomes this problem, allowing for more accurate testing by eliminating the influence of test lead resistance.

- 2 clamp measurement method  

Suitable for measuring at multiple points without the use of auxiliary electrodes.  

This method uses a voltage injection clamp and a clamp sensor to measure the current. Then, the ground resistance is calculated without inserting additional electrodes into the ground, making the operation quicker.  

- Low impedance measurement method  

This is a continuous check step after measuring earth resistance using the 3-pole method.  

When the electrodes are reconnected to the power system, a low resistance should be measured to ensure system continuity.

Optimal design:

- Fast measurement time, coils do not get tangled or twisted: The combination of the ability to display measurement values ​​after only 6 seconds (3-pole method) and easy-to-use coil design helps optimize working time job.  

- Only one insertion is required thanks to the maximum allowable resistance of up to 100 kΩ: This method uses an injection clamp to apply the voltage and a clamp sensor to measure the current, then calculate the ground resistance. There is no need to insert additional auxiliary electrodes into the soil, just attach two clamps to the electrode being measured.

- Take measurements even on concrete  

*Newly designed Earth Nets L9846 Module :This module serves as an auxiliary electrode specifically for flat surfaces where traditional pins cannot be used. When opened, two copper grids come into direct contact with the surface. Simply pour water on to measure earth resistance without any other electrode insertion.

Sensor pliers are ideal for tight spaces

When ground electrodes are installed in space-constrained areas or bus bars have large thicknesses, the CT9848 sensor pliers are the perfect choice. With a thin and wide pincer design, clamping ground electrodes is easy, gentle and effective even in the most difficult working conditions. 

Wireless support – Easily transmit measurement data

The Hioki FT6041, when combined with the Wireless Adapter Z3210 (purchased separately), allows measurement data to be transferred directly to a smartphone or tablet. Quickly create reports with images and drawings right on site.

GENNECT Cross application  

GENNECT Cross is free software developed by Hioki specifically for measuring devices. This application supports checking, managing data and creating reports easily. You can take photos of the measurement location, record measurement results directly on the image, add handwritten notes and store data scientifically, helping to optimize field workflow.

Related News

Checking Lithium Battery Temperature with an Infrared Thermometer
11/10/2026 16:45:58

An infrared thermometer is a useful tool for quickly checking the surface temperature of lithium batteries without direct contact. This method allows technicians to identify abnormal temperature areas, assess operating conditions, and inspect battery systems during maintenance.

How common is the selection of RBW on a spectrum analyzer?
11/10/2026 15:13:05

You are measuring an amplifier, and only one peak appears on the screen—even though there are clearly two carriers. Or, you know for a fact that harmonics are present, but the noise floor sits above them. Or, after making adjustments, the scanner slows down to the point where you find yourself waiting for each individual sweep. These three scenarios often share a common cause: the RBW (Resolution Bandwidth)

How Do Thermal Cameras Inspect PV System Faults?
11/10/2026 14:06:04

Thermal imaging helps inspection teams identify temperature anomalies associated with PV panel, connection, junction-box, inverter, and battery issues while the system is operating.

Vietnam’s Semiconductor Industry Outlook to 2030: Opportunities and Challenges
11/10/2026 11:22:48

Những khoản đầu tư mới, cùng định hướng phát triển công nghiệp bán dẫn đến năm 2030, đang tạo nền tảng cho thị trường trong nước. Tuy nhiên, để nâng cao vị thế trong chuỗi giá trị toàn cầu, Việt Nam cần giải quyết bài toán về công nghệ lõi, nhân lực kỹ thuật và năng lực đo kiểm.

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts