HV HIPOT GD6100 Insulation Oil Tan Delta Tester (1000V-2200V)
Manufacturer: HV HIPOT Model: GD6100 Origin: China Guarantee: 12 Month - Contact
Call for the best price
Hanoi city: (024) 35.381.269
Danang city: (023) 63.747.711
Bac Ninh city: (0222)730.39.68
HCM city: (028) 38.119.636
Conditions: -5 ℃ -40 ℃; RH <80%
Power Supply: AC 220V ± 10%
High voltage output: 1000V-2200V, every step 200V
Accuracy: 2%
Capacity: 50VA; Output Current is 25mA
Temperature induction furnace: Max. Power 500W
Temperature control range: <100 ℃
Temperature measurement error: ± 0.5 ℃
Temperature control error: ± 1 ℃
Temperature control time: less than 20min, indoor temperature to 90℃
Measure range:
- Tgδ: Unlimited
- Cx: 15pF-300pF
- Rx: 10M-10T
Accuracy:
- tgδ: ±1.0% of the reading + 0.020%
- Cx: ± 1.0% of the reading + 0.5pF
- Rx: 10% of the reading
Relative dielectric constant: εr: automatic calculation
Volume resistivity: ρ: automatic calculation
Dimensions: 450 (L)*310 (W)*360 (H)
Weight: 18kg
- Quality Engagement
- Easy change and return
- Delivery Avaliable
- Favorable payment