• Nominal voltage: ±100kV
• Rated level voltage: ±100kV
• Rated energy: 5kJ
• Impulse capacitance: 1µF
• Number of Levels: 1
• Rated level capacitance: 3µF(each impulse capacitor 1µF at 100kV, total 1piece)
• Impulse voltage waveform: generated when load capacitance is 300-3000pF.
• T1=1.2µs±30%, T2=50µs±20%, standard lightning impulse voltage full waveform of peak voltage deviation≤3%;
• Standard operation waveform 250±20%/2500±60%. These 2 Impulse voltage waveform parameters and error are accorded with national requirements of GB311.1and IEC60060 standard.
• Voltage utilization factor: Standard lightning impulse voltage waveform ≥90% when load capacitance is below 1000pF, standard operation impulse voltage waveform≥80% when load capacitance is below 2000pF.
• Standard operation impulse voltage waveform ≥70%.
• Locking range: level voltage is within the range of 20%-100%rated voltage, positive and negative
• locking range no less than 25%.
• Out-of-control rate of synchronous discharge: <5%
• Min.output voltage: ≥±20% of rated voltage.
• Instability of discharge voltage: <±1.0%
• Continuous time: Above 2/3 of rated voltage, continuous working when charge and discharge once every 120s. Below 2/3 of rated voltage, continuous working when charge and discharge once every 60s.