Measurement ranges (Pa): -250−2500 Pa
Communication: RS-485 Modbus (RTU)
Accuracy (from applied pressure) (model 2500): Pressure < 125 Pa = 1 % + ±2 Pa; Pressure > 125 Pa = 1 % + ±1 Pa
Measuring units: Pressure: Pa, kPa, mbar, inchWC, mmWC, psi; Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
Measuring element MEMS, no flow-through
Control signal: 0…10 VDC
PID-parameters: Selectable via menu and Modbus
Zero point calibration: via Modbus or by pushbutton
Supply voltage: 24 VDC ±10 % / 24 VAC ±10 %
Power consumption: < 1.0 W
Output signal: via Modbus
Operating temperature: -20…+50 °C
Protection standard: IP54