Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Measurement ranges (Pa): 0−7000 Pa
Accuracy (from applied pressure) : Pressure < 125 Pa = 1.5 % + ±2 Pa; Pressure > 125 Pa = 1.5 % + ±1 Pa
Zero point calibration: automatic with autozero element (-AZ) or by pushbutton
Measuring units: Pressure: Pa, kPa, mbar, inchWC, mmWC, psi; Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
Supply voltage: 24 VAC ±10 % / 24 VDC ±10 %
Power consumption: < 1,0 W
Output signals for pressure and air flow (selectable by jumper): 0…10 VDC / 2...10 VDC; 4…20 mA
Operating temperature: -20…+50 °C (with autozero calibration -5...+50 °C); -40...+50 °C (-40C model)
Response time: 1...20 s
Protection standard: IP54