HK Instruments Siro-PM-D Multifunctional indoor air quality transmitters for building automation systems (PM: 500 μg/m³)
Manufacturer: HK Instruments Model: Siro-PM-D P/N: 304.003.003 - Contact
Call for the best price
Hanoi city: (024) 35.381.269
Danang city: (023) 63.747.711
Bac Ninh city: (0222)730.39.68
HCM city: (028) 38.119.636
Measurement ranges:
+ PM1/PM2.5/PM10:
0–50 μg/m³ / 0–500 μg/m³ (selectable via jumper)
IAQ index: 1-5 (WHO rating)
Accuracy:
+ PM:
0…100 µg/m3:
PM2.5: ±15 µg/m³ (at 25 ⁰C ±5 ⁰C)
PM1/PM10*: ±25 µg/m³ (at 25 ⁰C ±5 ⁰C)
100…1000 µg/m3:
PM2.5: ±15 % (at 25 ⁰C ±5 ⁰C)
PM1/PM10*: ±25 % (at 25 ⁰C ±5 ⁰C)
*PM1 and PM10 values are calculated from PM2.5 measurement reading with the default particle distribution
Measuring elements:
+ CO2: Non-dispersive infrared (NDIR)
+ VOC: Complementary Metal Oxide Semiconductor (CMOS)
+ PM: Laser-based light scattering particle sensing
+ Temperature: Integrated to CMOS
+ Relative humidity: Thermoset polymer capacitive sensing element
Measuring units:
+ CO2: ppm
+ Relative humidity: % rH
+ Temperature: °C
+ VOC: CO2eq: ppm; TVOC: ppm, μg/m3
+ PM1/2.5/10: μg/m3
Calibration (CO2): Automatic self-calibration, ABC LogicTM
Supply voltage: 24 VDC/VAC ±10 %
Output signal 1–4:0...10 V (optional 2...10 V / 0...5 V, display or configuration tool required); Optional: 4...20 mA; Linear to selected measurement (CO2, VOC, PM, rH or Temp)
Operating temperature: 0...50 °C
Protection standard: IP20
Noted:
PM = Particulate Matter sensor
D = Display
- Quality Engagement
- Easy change and return
- Delivery Avaliable
- Favorable payment