HV HIPOT GDHG-103 CVT Calibration System
Manufacturer: HV HIPOT Model: GDHG-103 Origin: China Guarantee: 12 Month - Contact
Call for the best price
Hanoi city: (024) 35.381.269
Danang city: (023) 63.747.711
Bac Ninh city: (0222)730.39.68
HCM city: (028) 38.119.636
Specifications
Power supply: 220V±5V
Frequency: 50Hz±0.5Hz
Operation Temperature: 5℃-40℃
Relative humidity: <80%(at 25℃)
Altitude: <2500m
Measuring range
Cophase component(%): 0.0001-200.0, resolution: 0.0001
Quadrature component(min): 0.001-700.0, resolution: 0.001
Impedance(Ω): 0.001-20.0, resolution: 0.0001
Admittance(ms): 0.0001-20.0, resolution: 0.0001
Basic error
Cophase component: ΔX=±(X×2%+Y×2%)±Dx
Quadrature component: ΔY=±(X×2%+Y×2%×34.48)±Dy
X,Y-- Display value of instrument
Dx, Dy-- Quantization error
Dx=2, Dy=5
Error of Percent table: 1.5%
Operation range:
Current:
(1%-149%)In (In =5A)
(5%-149%)In (In =1A)
Voltage:
(5%-149%) Un (Un =100V, 150V, 100V/√3)
(5%-149%)Un (Un =100V/3)
Working load:
Current: TO/TX <0.12Ω, cosΦ=1
Voltage: a/x <0.25VA (100V)
Polarity instruction
When the current or voltage is at 5% of rated, error is over 180%, it will indicate polarity status.
Note: If the current is above 10% of rated current/voltage, but there is no polarity instruction, it means there is fault, please do not increase current or voltage.
Otherwise, the instrument will burn out.
Ratio instruction
When the current or voltage is above 5% of rated, error is over 30% and less than 180%, it will indicate ratio mistake.
Insulation and withstand voltage instruction:
Terminal TX and Ground terminal () is short circuit
The shell can withstand 1.5kV/1min voltage.
Power consumption: <25VA
Harmonic suppression ratio: >40db
Dimension: 260*350*150mm
Weight: about 6kg
- Quality Engagement
- Easy change and return
- Delivery Avaliable
- Favorable payment