Supply voltage
permissible range, lower limit (DC): 20.4 V
permissible range, upper limit (DC): 28.8 V
Input current
from backplane bus 5 V DC, max.: 140 mA
Digital outputs
from load voltage L+, max.: 16.7 mA/relay coil
Power loss
Power loss, typ.: 5 W
Digital outputs
Number of digital outputs: 8
in groups of 1
Short-circuit protection: No; to be provided externally
Switching capacity of the outputs
with resistive load, max.: 2 A
on lamp load, max.: 30 W with DC, 200 W with AC
Output voltage
Rated value (DC): 5 V DC to 30 V DC
Rated value (AC): 5 V AC to 250 V AC
Output current
for signal "1" rated value: 2 A
Output delay with resistive load
"0" to "1", max.: 10 ms
"1" to "0", max.: 10 ms
Total current of the outputs (per group)
horizontal installation — up to 50 °C, max.: 2 A; Current per mass
Relay outputs
Number of relay outputs: 8
Rated supply voltage of relay coil L+ (DC): 24 V
Number of operating cycles, max.: mechanically 10 million, at rated load voltage 100 000
Switching capacity of contacts
with inductive load, max.: 2 A
on lamp load, max.: 30 W with DC, 200 W with AC
with resistive load, max.: 2 A
Cable length
shielded, max.: 500 m
unshielded, max.: 150 m