Temperature - TC Type K (NiCr-Ni)
Measuring range: -40 to +1200 °C
Accuracy
±0.5 % of mv (Remaining Range)
±0.5 °C (0.0 to +100.0 °C)
Resolution
1 °C (Remaining Range)
0.1 °C (-40 to +999.9 °C)
Differential Pressure - Piezoresistive
Measuring range: -100 to +200 hPa
Accuracy
±1 % of mv (+50.1 to +100.0 hPa)
±0.5 hPa (0 to +50.0 hPa)
±1.5 % of mv (+100.1 to +200 hPa)
Resolution: 0.01 hPa
Flue gas O₂
Resolution: 0.1 Vol.%
Flue gas COlow (with H₂-compensation)
Measuring range: 0 to 500 ppm
Accuracy
±2 ppm (40 to +500 ppm)
±5 % of mv Remaining Range
Resolution: 0.1 ppm
Flue gas NO
Measuring range: 0 to 3000 ppm
Accuracy
±5 % of mv (101 to 2000 ppm)
±10 % of mv (2001 to 3000 ppm)
5 to 0 ppm
Resolution: 1 ppm
Flue gas Nolow
Measuring range: 0 to 300 ppm
Accuracy
±5 % of mv (40 to 300 ppm)
±2 ppm (0 to +39.9 ppm)
Resolution: 0.1 ppm
Differential Pressure flue gas Draught - Piezoresistive
Measuring range: -9.99 to +40 hPa
Accuracy
±0.02 hPa (0.1 to +3.00 hPa)
±1.5 % of mv (3.01 to +40 hPa)
±0.005 hPa (+0 to +0.1 hPa)
Resolution
0.001 hPa (0 to 0.1 hPa)
0.01 hPa (Remaining Range)
Flue gas degree of effectivity, Eta (calculated)
Measuring range: 0 to 120 %
Resolution: 0.1 %
Flue gas loss (calculated)
Measuring range: 0 to 99.9 %
Resolution: 0.1 %
Flue gas CO₂ calculation (calculated from O₂)
Measuring range: Display range 0 to CO₂ max
Accuracy: ±0.2 Vol.%
Resolution: 0.1 Vol.%
Flue gas CO (without H₂-compensation)
Measuring range: 0 to 4000 ppm
Accuracy
±5 % of mv (401 to 2000 ppm)
±10 % of mv (2001 to 4000 ppm)
±20 ppm (0 to 400 ppm)
Resolution: 1 ppm
Ambient CO
Measuring range: 0 to 2000 ppm
Accuracy
±10 % of mv (101 to 2000 ppm)
±10 ppm (0 to 100 ppm)
Resolution: 1 ppm
General technical data
Operating humidity: 15 to 90 %RH non-condensing
Weight: approximately 800 g
Dimensions: 244 (including probe connection) x 98 x 59 mm (LxWxH)
Operating temperature: -5 to +45 °C
Protection class: IP40
Display type: 5.0" touch display, HD 1280*720 pixels, IPS (160 k)
Power supply: Rechargeable battery, USB mains unit
Memory: 1,000,000 measuring values
Battery life: 10 h
Storage battery type: Lithium ion battery
Storage temperature: -20 to +50 °C
Charging temperature: 0 to +45 °C
Differential Pressure 4 Pa measurement - Piezoresistive
Measuring Range: -50 to +50 Pa
Accuracy
±0.3 Pa (< 10 Pa)
±3 % of mv (Remaining Range)
Resolution: 0.1 Pa
Compact basic flue gas probe
Diameter probe shaft: 6 mm
Cable length: 1.5 m
Length probe shaft: 180 mm
Temperature maximum: 500 °C
Diameter: 6 mm
Weight: 346 g
Instrument case (height: 130 mm)